Transducers for Pt-100 and Resistors
General Description
These transducers convert the resistance of a resistive sensor (e.g., Pt-100) to a temperature or resistance dependant linear signal (e.g., 0-10 V or 4-20 mA) or into a frequency output (IR 370, max. 10 kHz). The measurement range and zero-point of the DIL-programmabale transducers are selected by DIL-switches in steps of 10° or 10 Ohm using simple binary codes (10, 20, 40, ...). Various operating modes can also be selected via DIL-switches (2-, 3-, or 4-wire connection, voltage or current output). All settings are calibrated.
Our newest generation of programmable transducers (IR 3XX) allow the setting of almost any desirable range via a RS232-interface. This interface allows also the download of measurement values (AD-converter), calibration date, serial number and more.
- With optional galvanic isolation of input and output, 2- or 3-port isolation, test voltage 1-3 kV.
- Linearization for Pt-100/1000.
- Fixed-range types: Input and output ranges selectable as desired, factory calibrated.
- Programmable types: all ranges and settings can be selected via DIL-switches (depending on module).
- Different housings available.
- Secure against short circuits, connection reversal, up to 30 VDC overvoltage.
- Many options: Different isolaton classes, limit switch, multiplexer, digital interface, frequency output, PWM output.
Overview/Prices
![]() |
Modules for DIN-Heads (Type B) |
||
Type | Output | Power supply | Range |
---|---|---|---|
RTM 40/41 | 4-20mA | 2-D, 12-30V | fixed |
![]() |
Printed Circuit Board Modules |
||
Type | Output | Power supply | Range |
---|---|---|---|
RTM 10/11 | V | 14-30V/ ±15V | fixed |
RTM 30/31 | 4-20mA | 2-D, 12-30V | fixed |
RTM 32/33 | 0/4-20mA | 14-30V | fixed |
RTM 60 | V | ±15V | fixed |
Abbreviations:
Iso.: Transducer with galvanic isolation between input and output (option: 3-port isolation).
2-D: 2-wire module (4-20 mA), power supply and signal over the same wire.
3P: 3-port-isolation (including power supply), test voltage 1 to 3 kV depending on module.
fixed: input and output range selected as desired (required range to be specified when ordering).
fixed (RS232): input and output range selected as desired (required range to be specified when ordering), programming only in factory, option: potentiometer.
progr. (DIL): User programmable module (via DIL switches), with potentiometer.
When ordering, please specify:
- module type
- accuracy class (A, C, or D)
- input range (in °C, K or Ohm)
- output range (in mA, V or Hz)
- supply voltage (in V, uni- or bipolar)
- Only the module type and accuracy class (A, C or D) has to be specified for programmable versions. If required, module can be precisely set for a specific range.